Pipe Weight Calculator: steel pipe by NPS and schedule

How it's calculated. Steel pipe weight per foot = 10.69 × (OD − wall) × wall, with the outside diameter and wall in inches: the same as π ÷ 4 × (OD² − ID²) × 3.40 lb.
NPS 2 Sch 40: OD 2.375", wall 0.154" → 3.66 lb/ft × 21' = 76.8 lb
01

Shape and size

Schedule
02

Material

490 lb/ft³Density
03

Length and quantity

ftin
Total weight
76.8lb
Pipe NPS 2 Sch 40 · Carbon steel
Weight per foot3.66 lb/ft
Total length21' 0"
Section area1.075 in²
Inside diameter2⅛"
Holds3.7 gal
Weight full of water107.3 lb
Weight from the nominal size at the listed density

Cross-section

Pipe NPS 2 Sch 40 · Carbon steel
SECTION⌀ 2⅜"t = ⅛"DELIMETRA · FT-IN
weight = area × length × densityFormula1.075 in²Section area490 lb/ft³Density
Your local prices
$
$
$

Prices are not pre-filled: metal prices change by the week and by the supplier.

How we calculate

Weight = cross-section area × length × density. Steel is taken at 490 lb/ft³ (7,850 kg/m³), the value behind the standard weight tables.

Areas: round π·d²÷4; hexagon 0.866·s²; angle (A + B − t)·t; channel d·t + 2(b − t)·t; pipe π(OD² − ID²)÷4; rectangular tube with rounded corners, outside radius 2t, as in the AISC Manual.

Rolled angles and channels have rounded and tapered parts, so their book weight can differ from these simple sections by a few percent; use the mill's figure when it matters.

Pipe sizes follow ASME B36.10: NPS is a name, not a measurement, and each size has one outside diameter whatever its schedule.

Total
76.8lb

A 21 ft length of 2 inch Schedule 40 steel pipe weighs about 77 lb: 3.66 lb per foot. Full of water it weighs 107 lb, because it holds 3.7 gallons. The calculator above does this for any NPS from ½ to 12 in Schedule 40 or 80, or for any outside diameter and wall, in steel, stainless, aluminum, copper, brass, cast iron, PVC, HDPE or polypropylene.

How the calculator works

Choose the pipe size and schedule, or "Other outside diameter" for tubing and odd sizes, then the material, the length of one piece and how many. The result is the total weight, weight per foot, one piece, the cross-section area of the wall, the inside diameter, how much the pipe holds and what it weighs full of water.

The formula

The wall is a ring: area = π ÷ 4 × (OD² − ID²), with ID = OD − 2 × wall. For steel at 490 lb/ft³ this simplifies to the formula in the standard: lb per foot = 10.69 × (OD − wall) × wall, in inches. For NPS 4 Schedule 40: 10.69 × (4.500 − 0.237) × 0.237 = 10.8 lb per foot, the plain-end weight in ASME B36.10.

NPS is a name, not a size

Nominal pipe size does not measure anything. Up to NPS 12 the outside diameter is larger than the number, and every schedule of one size has the same outside diameter: the extra wall of Schedule 80 goes inside, so the bore gets smaller. That is why fittings fit any schedule of the same size.

NPSOutside diameter, inSch 40 wall, inSch 40, lb/ftSch 80, lb/ftWater, gal/ft (Sch 40)
½0.8400.1090.851.090.016
¾1.0500.1131.131.480.028
11.3150.1331.682.170.045
1½1.9000.1452.723.640.106
22.3750.1543.665.030.174
33.5000.2167.5810.260.384
44.5000.23710.8015.000.661
66.6250.28018.9928.601.501
88.6250.32228.5843.432.599
1212.7500.40653.5888.725.815

Dimensions from ASME B36.10; weights computed at 490 lb/ft³ and within 0.2 % of the tabulated plain-end weights. Threaded and coupled pipe weighs a little more.

Capacity and weight full of water

The bore holds π ÷ 4 × ID² per unit length: in gallons per foot, 0.0408 × ID². Water weighs 8.34 lb per gallon. Pipe supports and hangers carry the pipe and its contents, so the weight full of water is the one to use for spacing hangers or sizing a rack.

Plastic and other metals

PVC Schedule 40 and 80 use the same outside diameters as steel (iron pipe size, ASTM D1785), so the size list works for them too; PVC weighs about 18 % of steel, HDPE and polypropylene about 12 %. Stainless pipe follows ASME B36.19 with its own thin schedules (5S, 10S) but the same outside diameters; enter the wall for those. Copper tube for plumbing is sized differently (types K, L and M); use "Other outside diameter".

Common mistakes

For square and rectangular tubing, see the Tube Weight Calculator; for bar, plate and angle, the Steel Weight Calculator.

Questions

How much does 2 inch Schedule 40 steel pipe weigh?

About 3.65 lb per foot: OD 2.375 in, wall 0.154 in. A 21 ft length weighs about 77 lb, and about 107 lb full of water.

What is the formula for steel pipe weight?

lb/ft = 10.69 × (OD − wall) × wall, with OD and wall in inches. For NPS 4 Sch 40: 10.69 × (4.5 − 0.237) × 0.237 = 10.8 lb/ft.

What is the difference between Schedule 40 and Schedule 80?

Same outside diameter, thicker wall: NPS 2 Sch 80 has a 0.218 in wall against 0.154 in, weighs 5.02 lb/ft against 3.65, and has a smaller bore.

Is NPS the actual size of the pipe?

No. NPS is a name. Up to NPS 12 the outside diameter is larger than the number: NPS 2 is 2.375 in outside, NPS ½ is 0.840 in.

How much water does a pipe hold?

Gallons per foot = 0.0408 × ID² with ID in inches. NPS 2 Sch 40 (ID 2.067 in) holds 0.174 gallons per foot, 1.45 lb of water.

How much does PVC pipe weigh?

Schedule 40 PVC has the same dimensions as steel Schedule 40 but weighs about 18 % as much: NPS 2 is about 0.65 lb per foot.