A 10 ft beam made of two 2×12 Douglas Fir No. 2 boards carrying 300 lb per foot sags about 0.12 inch at mid-span, about L/1,000, well inside the L/360 floor limit of 0.33 inch, and uses about 80 % of its bending strength. The calculator above checks any beam like this: any span, four kinds of supports, any number of uniform and point loads, in lumber, LVL, a steel W-beam or steel tube, with the moment, shear and deflection diagrams.
How the calculator works
Set the supports and the span. Add the loads as you know them: a uniform load in pounds per foot over all or part of the span, or point loads at given distances; the beam's own weight can be added. Choose the beam: lumber species, grade, size and plies; LVL depth and plies; a W-shape; a steel tube; or your own E, I and S. Pick the deflection limit. The result is the deflection and its L/ ratio, the maximum moment and shear, the reactions, the share of bending and shear strength used and, when the beam fails, the smallest member of the same kind that works.
Deflection formulas
| Beam and load | Maximum deflection | Maximum moment |
|---|---|---|
| Simple span, uniform load w | 5wL⁴ ÷ 384EI | wL² ÷ 8 |
| Simple span, point load P at mid-span | PL³ ÷ 48EI | PL ÷ 4 |
| Cantilever, uniform load | wL⁴ ÷ 8EI | wL² ÷ 2 |
| Fixed both ends, uniform load | wL⁴ ÷ 384EI | wL² ÷ 12 |
For any mix of loads and supports the calculator solves the beam by the finite element method; for the cases in the table it gives exactly these results. E is the stiffness of the material, I the moment of inertia of the section: a beam twice as deep is eight times stiffer.
Deflection limits
IBC Table 1604.3 limits floor members to L/360 under live load and L/240 under total load, roof members to L/240 or L/180 depending on the ceiling below, and L/360 where plaster or stucco would crack. For a cantilever, L in the ratio is twice its length. Under ceramic tile L/480 is a common target, under natural stone L/600 or stiffer.
Strength
- Lumber: bending stress M ÷ S against Fb from the American Wood Council's design values for joists and rafters. Those values include the 15 % repetitive member factor of NDS 4.3.9, which applies to joists at 24 inches or closer and to three or more plies in contact; a single or two-ply beam or header does not get it. Shear 1.5 V ÷ (b × d) against Fv from the NDS Supplement: 180 psi for Douglas Fir-Larch, 175 Southern Pine, 150 Hem-Fir, 135 Spruce-Pine-Fir.
- LVL: typical 2.0E values: Fb 2,600 psi at 12 inch depth, less for deeper members, Fv 285 psi, E 2,000,000 psi. Manufacturers publish their own tables, and theirs govern.
- Steel: allowable moment Fy × Zx ÷ 1.67 (AISC 360, sections F2 and F7) for compact W-shapes and tubes whose top flange is braced along its length, as it is under a floor or deck. A beam unbraced over a long length can buckle sideways at a lower load; that is not checked.
Loads
A beam carries the floor or roof halfway to the next support on each side. Multiply the load per square foot by that width: a floor beam carrying 6 ft of floor at 40 psf live and 10 psf dead takes 300 lb per foot. The calculator uses the loads as entered (allowable stress design), so enter the service loads, not factored ones.
What it does not check
Bearing at the supports, connections, lateral bracing of steel, notches and holes, wet or treated lumber and long-term creep are left to the designer. Many building departments want an engineer's calculation for beams in a house; use this to compare options and see which size to ask about. For floor joists and rafters by the span tables, the Joist Span Calculator and Rafter Span Calculator are quicker.