Heating BTU Calculator: room heat loss and heater size

How it's calculated. For each surface, heat loss = area × (indoor − outdoor temperature) ÷ R-value; air leakage adds 1.08 × cfm × ΔT.
12 × 14 ft room, 2×4 R-13 walls, 70 °F inside, 0 °F outside: 4,368 Btu/h
01

Room

ft²
ftin
ft²
ft²
ft²
02

Walls

Cavity insulation
Continuous insulation (foam board)

Wall R 11.8 h·ft²·°F/BTU

03

Windows, floor and ceiling

Windows
Below the room
Above the room
04

Temperatures and air leakage

°F
°F
Heat loss
4,368Btu/h · 1.28 kW
168 ft² · 2×4 wood frame · ΔT 70 °F
Walls993 Btu/h
Windows704 Btu/h
Doors493 Btu/h
Floor1,036 Btu/h
Ceiling296 Btu/h
Air leakage846 Btu/h
Heat loss4,368 Btu/h
Per square foot26 Btu/h·ft²
Heater size with 20 % margin5,242 Btu/h · 1.5 kW
Electric baseboard at 250 W/ft6 ft
Wall R-value11.8 h·ft²·°F/BTU
Window U-factor0.5 BTU/(h·ft²·°F)
Heat loss = area × ΔT ÷ R for each surface + air leakage

Where the heat goes

168 ft² · 2×4 wood frame · ΔT 70 °F
ROOM SECTION70 °FCeiling296 Btu/hFloor1,036 Btu/hWalls993 Btu/hWindows704 Btu/hDoors493 Btu/hAir leakage846 Btu/h0 °FSHARE OF THE LOSSWalls23 %Windows16 %Doors11 %Floor24 %Ceiling7 %Air leakage19 %DELIMETRA · BTU/H
A × ΔT ÷ R + 1.08 × cfm × ΔTQ26 Btu/h·ft²Per square foot5,242 Btu/hHeater size with 20 % margin6 ftElectric baseboard at 250 W/ft
How we calculate

Each surface loses Q = area × ΔT ÷ R, where ΔT is the indoor minus the outdoor design temperature and R the surface's total thermal resistance including air films. Windows and doors are taken off the gross wall area.

Wood frame walls by the parallel path: 25 % of the wall is studs (R-1.25 per inch), 75 % insulated cavity; drywall, sheathing, siding and air films add R-2.5. A 2×4 wall with R-13 batts works out to about R-11.9. Solid walls: thickness ÷ λ plus any added insulation.

Windows: single pane U 1.04, double U 0.50, triple U 0.34, low-e double U 0.25 (Btu/h·ft²·°F). Floors: slab R-11, over an unheated basement R-5.7, over a crawlspace or outdoors R-2.8. An attic ceiling adds R-1.7 of films and drywall to its insulation; the attic is taken at the outdoor temperature.

Air leakage: room volume × air changes per hour × 1.08 × ΔT (0.018 Btu per ft³ per °F). The equipment margin of 20 % follows our earlier calculator; for a whole house use an ACCA Manual J calculation.

Heat loss
4,368Btu/h

A 12 × 14 ft corner bedroom with 8 ft ceilings, 2×4 walls with R-13 batts, 20 ft² of double-pane windows, an exterior door, a slab floor and an R-38 attic loses 4,368 Btu/h when it is 70 °F inside and 0 °F outside — 26 Btu/h per square foot. A heater with a 20 % margin is 5,242 Btu/h, or about 6 ft of electric baseboard. The calculator above works this out for any room and wall.

How the calculator works

Enter the floor area, ceiling height and the area of the exterior walls, windows and doors, pick the wall, glazing, floor and ceiling, then set the indoor and outdoor design temperatures and how tight the room is. The result is the loss through each surface, the total in Btu/h and kW, the heater size and the baseboard length.

Where the heat goes in the example

SurfaceR-valueBtu/h
Walls, 168 ft² netR-11.9 (2×4, R-13)993
Windows, 20 ft²U 0.50704
Door, 20 ft²R-2.8493
Slab floor, 168 ft²R-11.41,036
Ceiling, R-38 atticR-39.7296
Air leakage, 0.5 ACH—846
Total4,368

Walls

A wood frame wall is not as good as its batts: about a quarter of it is studs at R-1.25 per inch. With drywall, sheathing, siding and air films, a 2×4 wall with R-13 works out to R-11.9, R-15 to R-12.7, and a 2×6 wall with R-21 to R-17.1 (R-22.9 with R-5 foam outside). Solid walls — brick, concrete, aerated concrete, logs, SIPs — are counted by thickness and conductivity, plus any insulation you add.

Windows and design temperature

Windows lose the most per square foot: changing the example to low-e glass saves 352 Btu/h, single pane adds 746. The outdoor temperature is the 99 % heating design temperature for your location, not the record low: at 20 °F outside the same room loses 3,120 Btu/h.

Better walls and attic cut the loss before you buy equipment — see the Insulation Calculator. For summer, size the cooling with the AC BTU Calculator; fresh air is in the CFM Calculator, and room areas in the Square Footage Calculator.

Questions

How many BTU do I need to heat a room?

About 20–40 Btu/h per square foot in cold climates, depending on walls, windows and how cold it gets. A 168 ft² room with R-13 walls at 0 °F outside needs 4,368 Btu/h.

How do I calculate heat loss?

Heat loss = area × temperature difference ÷ R-value for each wall, window, door, floor and ceiling, plus 1.08 × cfm × ΔT for air leakage.

What outdoor temperature should I use?

The 99 % heating design temperature for your location from ACCA Manual J or ASHRAE climatic data — it is colder than 99 % of the hours in a year, not the record low.

How many feet of baseboard heater do I need?

Heat loss in watts ÷ 250 W per foot. 4,368 Btu/h is 1,280 W, so about 5–6 ft of baseboard.

Should I add a margin to the heater size?

A 20 % margin covers recovery after setback; for a furnace or heat pump for the whole house, use an ACCA Manual J calculation rather than a bigger margin.

Related calculators